Cooling coil condensate and air load calculator

Compare entered inlet and outlet air states to estimate water removal and moist-air enthalpy reduction at a supplied dry-air mass flow.

Your numbers

Calculated on your device. Your inputs aren’t sent to us.

Your result

Ready when you are

Enter your inputs and select Calculate.

Try it, understand it

Explore the result

Compare entered inlet and outlet air states to estimate water removal and moist-air enthalpy reduction at a supplied dry-air mass flow.

Worked example comparison
ExampleOutputWhat to notice
Worked exampleIdeal condensate removal23.248643 kg/hThe example cools 30 °C air at sixty-percent RH to 15 °C at ninety-percent RH, at 101.325 kPa and one kilogram per second of dry air. Despite the higher outlet RH, the outlet humidity ratio is lower. The state difference produces roughly 23.25 kg/h of ideal condensate and about 31.87 kW of moist-air enthalpy reduction. Keeping inlet and outlet states identical should return zero removal and zero enthalpy reduction.
Change the explicit assumptionIdeal condensate removal0 kg/hChange outlet, outletRh while holding the other entries fixed; inspect the table and the model limits.

Check your understanding

Can outlet RH exceed inlet RH while water is removed?

Yes. RH is temperature-dependent; humidity ratio is the relevant mass comparison.

Does this predict the coil leaving temperature?

No. Both states are supplied, so the page calculates the consequences of that scenario.

Behind the numbers

How this calculation works

Relative humidity can rise while air loses water because cooling lowers its saturation pressure. A moisture-removal calculation must compare humidity ratios, not simply subtract the two RH percentages.

THE FORMULACondensate kg/h = dry-air kg/s × (inlet humidity ratio − outlet ratio) × 3600; enthalpy reduction kW = dry-air kg/s × (hin − hout)

A worked example

The example cools 30 °C air at sixty-percent RH to 15 °C at ninety-percent RH, at 101.325 kPa and one kilogram per second of dry air. Despite the higher outlet RH, the outlet humidity ratio is lower. The state difference produces roughly 23.25 kg/h of ideal condensate and about 31.87 kW of moist-air enthalpy reduction. Keeping inlet and outlet states identical should return zero removal and zero enthalpy reduction.

Good to know

Entered-state ideal moist-air balance only; no coil selection, bypass factor, condensate piping capacity or equipment guarantee. Saturation pressure is approximated over liquid water within the supported temperature range. Real property data and the full equipment balance may be needed for design.

What the model answers

Relative humidity can rise while air loses water because cooling lowers its saturation pressure. A moisture-removal calculation must compare humidity ratios, not simply subtract the two RH percentages.

This page accepts both air states rather than predicting what a coil will produce. Dry-air mass flow then connects the per-kilogram state differences to a water-removal rate and an energy-rate estimate.

The Humidity ratio and moist air properties calculator explains each state’s vapor pressure, dry-air basis and enthalpy convention before the two states are compared here.

Measure and enter consistently

Use total absolute pressure for both states and a dry-air mass flow, not an unconverted moist-air mass or cubic-metre flow. The companion property calculator can help interpret the dry-air basis.

The supported cooling scenario cannot increase dry-bulb temperature, humidity ratio or moist-air enthalpy. Reheat, humidification and other processes need a different combination of state changes and energy terms.

Interpret the result

Enthalpy reduction uses the conventional moist-air reference. It excludes a separate sensible-enthalpy correction for leaving liquid condensate and any fan heat. It should not be presented as a complete coil plant duty under all conditions.

A sensible approximation is shown using inlet humidity ratio. The difference between total enthalpy reduction and that approximation is a residual, not an exact latent-heat decomposition. Actual apparatus dew point and bypass are not solved.

Work through the numbers

The example cools 30 °C air at sixty-percent RH to 15 °C at ninety-percent RH, at 101.325 kPa and one kilogram per second of dry air. Despite the higher outlet RH, the outlet humidity ratio is lower.

The state difference produces roughly 23.25 kg/h of ideal condensate and about 31.87 kW of moist-air enthalpy reduction. Keeping inlet and outlet states identical should return zero removal and zero enthalpy reduction.

Where this model stops

Entered-state ideal moist-air balance only; no coil selection, bypass factor, condensate piping capacity or equipment guarantee.

Saturation pressure is approximated over liquid water within the supported temperature range. Real property data and the full equipment balance may be needed for design.

A few questions, answered

Can outlet RH exceed inlet RH while water is removed?

Yes. RH is temperature-dependent; humidity ratio is the relevant mass comparison.

Does this predict the coil leaving temperature?

No. Both states are supplied, so the page calculates the consequences of that scenario.