Ideal transformer turns voltage and current calculator

Relate RMS voltages and currents with explicit turns counts and load apparent power in VA.

Your numbers

VA is not automatically real watts. All results use an ideal AC transformer with no losses or magnetizing current.

Calculated on your device. Your inputs aren’t sent to us.

Your result

Ready when you are

Enter your numbers and select Calculate.

Try it, understand it

Explore the result

Explore an ideal AC turns ratio with load specified as apparent power.

Worked example comparison
ExampleOutputWhat to notice
Twice the secondary turnsIdeal secondary RMS voltage460 V500 primary and 1,000 secondary turns give 460 V RMS from an entered 230 V RMS.
Equal turnsIdeal secondary RMS voltage230 VEqual 500-turn windings give equal ideal RMS voltages and load currents.
No load VAIdeal secondary RMS voltage460 VZero load VA gives zero load current in the idealization, without predicting real magnetizing current.

Check your understanding

Does twice the voltage mean twice the power?

No. For the same ideal apparent power the corresponding current halves.

Is a 100 VA input automatically 100 W?

No. Real power requires the appropriate power factor.

Behind the numbers

How this calculation works

Use an ideal AC turns ratio for RMS voltage and equal apparent-power magnitudes for the corresponding load currents. Keep VA separate from real power and do not infer a hardware rating.

THE FORMULAVs/Vp = Ns/Np; |Ip| = S/Vp; |Is| = S/Vs

A worked example

500 primary turns and 1,000 secondary turns give a ratio of 2. With 230 V RMS on the primary, ideal secondary voltage is 460 V RMS. At an entered 100 VA load, primary current is about 0.434783 A and secondary current about 0.217391 A.

Good to know

Ideal AC magnitudes only: no loss, magnetizing current, saturation, winding resistance, frequency/flux, insulation, phase group or rating model. Steady DC operation is not implied. Zero load VA is not a prediction of real no-load consumption.

A turns ratio changes voltage and current in opposite directions

The default 1,000 secondary turns over 500 primary turns gives a ratio of two. At 230 V RMS primary voltage, the ideal secondary is 460 V RMS. With an entered 100 VA load, the secondary current is about 0.217391 A and the primary current about 0.434783 A.

The higher ideal output voltage is accompanied by lower current for the same apparent power. It is not a doubling of energy. The model omits losses and magnetizing current, so it cannot predict a real transformer’s heating, regulation or no-load consumption.

The electrical power calculator uses a DC relationship. The ideal transformer here uses AC RMS magnitudes and load apparent power in VA.

VA is not automatically real watts

The entered load is apparent power, the product of RMS voltage and current magnitudes. Real power also depends on the load’s power factor. Treating the VA input as watts without that additional condition would add an assumption the calculator has not made.

The table varies primary voltage while holding the same apparent-power load and turn counts. Current therefore changes inversely with voltage. That is a set of fixed-VA scenarios, not a prediction for one fixed resistor whose power would change with voltage.

Ideal AC ratios do not specify a physical transformer design

Positive whole turn counts define a ratio but do not determine a core, frequency range, flux density, insulation or winding rating. This AC model does not imply that steady DC produces the same transformed output. Zero entered load gives zero load current in the idealization; real magnetizing current is not calculated.

The electrical power calculator uses a separate DC voltage-times-current relationship. The battery nominal energy and runtime calculator uses another constant-voltage energy budget. Neither supplies the omitted magnetic, AC or thermal details needed to turn this turns-ratio exercise into an equipment selection.

A few questions, answered

Does a step-up ratio increase power?

Not in the ideal model. Voltage increases while the corresponding current decreases for the same apparent power.

Is the load input in watts?

It is VA. Real watts require the appropriate load power factor.

Does zero load mean a real transformer draws nothing?

No. The model omits magnetizing current and no-load losses.

Can the AC relationship be applied directly to steady DC?

No. The supported model is an ideal AC transformer, without a magnetic-design calculation.